DC POWER SUPPLIES
DC Power Supply
Provides 24 Vdc to the control electronics for MicroFUSION, ATOM, and other power controllers.
An ultra precise, compact, and digital SCR power controller that adapts to both analog and digital environments, featuring two performance options.
An industrial Ethernet communication protocol used for real-time automation and factory control systems.
A simple industrial communication protocol used to connect PLCs, sensors, meters, and automation devices.
An industrial Ethernet standard used for communication between controllers and automation equipment.
Indicates the device can safely withstand up to 100,000 amps of short-circuit current.
Indicates the product complies with European Union safety, health, and environmental requirements.
Confirms the product meets electromagnetic interference standards in the United States.
MicroFUSION is a compact, high performance, microprocessor-based power controller available in single phase or three phase models to assist with control of AC loads.
Resistive or transformer-connected loads can be controlled in multiple ways, including Phase Angle, Zero Cross, Zero Cross Transformer (ZCT), or Fast Zero Cross (FZC). Output is controlled linearly and can be set to the average or RMS value of the voltage, current, and power.
MicroFUSION Three Phase controllers offer the following features:
Two Performance Options
MicroFUSION is available with one of two circuit boards. SX is a lower-cost alternative, whereas HX is a fully populated board that can be field-upgraded to include retransmits and other features. Available options with HX include:
OEM options may be available upon factory consultation.



| Phase | Three |
| Firing Mode |
Phase Angle Zero Cross Zero Cross Transformer Fast Zero Cross *More options available upon factory consultation |
| Output | AC |
| Amp Sizes | 8A, 16A, 32A, 50A, 80A, 100A, 130A, 160A, 200A, 240A, 320A, 400A |
| Voltage |
24-690 VAC (CE) 24-600 VAC (UL) 45-65 Hz |
| Control | Analog or Digital |
| Feedback Type |
Voltage Current Power External *More options available upon factory consultation |
| Retransmit |
Load Voltage Load Current Load Power Load Resistance |
| Limits |
Voltage Current Power |
| Alarms |
Overtemp Shorted SCR Communications Loss Current Limit Open Load Overcurrent trip Partial Load Fault Power Limit Voltage Limit Phase Loss |
| Additional Features |
Adjustable soft start Missing cycle detection Sync-Guard Trans-Guard |
| Mean Time Between Failures | >50,000 hours |
| Line Voltage (Auto Ranging) |
UL/cUL: 24 – 600 Vac (Nominal) (+10% / -15%) (Contact CCI for other options) CE: 24 – 690 Vac (Nominal) (+10% / -15%) (Contact CCI for other options) |
| Line Frequency (Auto Ranging) | 45 – 65 Hz |
| Frame Current Ratings (Amps) | Continuous RMS (AC): 8A, 16A, 32A, 50A, 80A, 100A, 130A, 160A, 200A, 240A, 320A, 400A |
| Current Rating – Peak Surge | 20x frame rating for 10 ms |
| Minimum Hold/Latch Current | 500 mA up to 160 A 1 A at 200 – 400 A |
| Max Leakage Current | 10.6 mA @ 600 Vac 50/60 Hz |
| SCR Rating (PIV) | 1600 V peak forward & reverse |
| Fusing | Optional external Class T, branch-rated, touch-safe fusing |
| Thermal | Integrated heat sink thermal sensor |
| Current Limit % of Frame Amp Rating |
Default 105% is only option for model SX-S Adjustable 20 – 105% for models SX-L and HX |
| Current Trip | 50 – 450% of continuous rating |
| Power Dissipation | 1.3 W per A of load current per phase |
|
Control Power / Operates Internal Control Electronics |
24 Vdc (+10 / -15%) |
| Surrounding Air Operating Temperature | 32 to 122°F [0 to 50°C] with derating for 140°F [60°C] |
| Humidity | 20% to 90% RH Non-Condensing |
| Rated Operating Altitude | Up to 6000 ft [1829 m] at full rated current |
| Contaminates |
RoHS Compliant CE Pollution Degree 2 (only non-conductive pollution occurs) |
| Storage Temperature | -4 to 176°F [-20 to 80°C] |
| Standard Performance | High Performance Option | |
|---|---|---|
| Setpoint Resolution | 10k | 10k or 64k |
|
Internal Control Loop Resolution |
16k | 64k |
| Output Resolution | 12k @ 50 Hz, 10k @ 60 Hz | 50k @ 50 Hz, 42k @ 60 Hz |
| Response Time | Adjustable from 50 ms to 2 s | Adjustable from 50 ms to 2 s |
| Voltage | 3.0% of frame rating | 0.5% of frame rating |
| Current | 3.0% of frame rating | 0.5% of frame rating |
| Power | 3.0% of frame rating | 1.0% of frame rating |
| Output Linearity | 4.0% from (5 – 100%) output range | 1.0% from (5 – 100%) output range |
| Accuracy | (+10% / -15%) line voltage change will result in a max output change of 0.5% from (5 – 100%) output range | +10% to -15% line voltage change will result in a max output change of 0.05% from (5 – 100%) output range |
| Temperature Drift | Output shall not change greater than 0.5% per degree C max over the operating temperature range from (5 – 100%) output range | Output shall not change greater than 0.2% per degree C max over the operating temperature range from (5 – 100%) output range |
| Software and Fieldbus Files – EtherNET/IP, PROFINET, Modbus TCP, EtherCAT | |
|---|---|
| Control Panel Software | Download |
| MicroFUSION EtherNet/IP EDS | Download |
| MicroFUSION PROFINET GSDML | Download |